Conventional type: AMS-12
■ AMS-12 switch cabinet is small-sized armored air-insulation switchgear and can effectively save space.
■ AMS-12 switch cabinet has central design and is equipped with VEP-12 indoor medium-voltage fixed and enclosed vacuum circuit breaker.
■ AMS-12 switch cabinet possesses sufficient space for cable connection.
■ AMS-12 switch cabinet is equipped with earth switch that possesses short-circuit making capacity and quick closing function.
Motor-operated type: AMS-12-M
■ The circuit breaker and earth switch of AMS-12-M switch cabinet are equipped with motor-operated device and can realize unattended transformer substation. The motor-operated device possesses electric machinery overload protection function and extended functions including hand operation precedence and closing interlock, and operates steadily and reliably.
Intelligent type: AMS-12-I
■ AMS-12-I switch cabinet is equipped with intelligent circuit breaker and combined electronic current-voltage transformer and realizes online status monitoring.
■ AMS-12-I switch cabinet is equipped with AP332 comprehensive intelligent unit and can comprehensively realize multiple functions such as measurement, monitoring, control, protection, communication and status detection. The communication agreement supports IEC61850 and satisfies communication standards of intelligent transformer substation.
■ AMS-12-I can realize programmed control as well as switch between power cut, power supply, overhaul and maintenance and standby status, thus improving reliability and operative efficiency.
■ AMS-12-I switch cabinet is equipped with infrared temperature sensor and can realize online monitoring of inlet and outlet bus temperature.
■ AMS-12-I switch cabinet is equipped with temperature & humidity sensor and can realize online monitoring of cabinet temperature and humidity
■ AMS-12-I switch cabinet possesses the function of arc protection and can realize quick failure isolation to save operating personnel's life and guarantee safety of the equipment.
Item
Unit
Data
Rated voltage
kV
3.6/7.2/12
Rated frequency
Hz
50
Rated power frequency withstand voltage (1min)
kV
42
Rated lightning surge withstand voltage (peak value)
kV
75
Rated current
A
630
1250
630
1250
1600
2000
2500
3150
630
1250
1600
2000
2500
3150
4000*
1250
1600
2000
2500
3150
4000*
1250
1600
2000
2500
3150
4000*
Rated short-circuit breaking current
kA
20
25
31.5
40
50
Rated short time withstand current (4s)
kA
20
25
31.5
40
50
Rated short-circuit making current (peak value)
kA
50
63
80
125
150
Rated peak withstand current (peak value)
kA
50
63
80
125
150
Opening times of rated short circuit current
Times
50 (40kA and below)
30 (50kA)
O-0.3s-CO-15s-CO (40kA and below)
O-0.3s-CO-180s-CO (40kA and below)
Rated operation order, non-automatic reclosing
O-180s-CO-180s-CO (50kA)
Rated operating voltage
V
AC220/110 DC220/110
Mechanical life
Times
30,000 (31.5kA and below)
20,000 (40kA and above)
※Rated voltage of motor-operated chassis vehicle motor
V
DC220/110, AC220/110
Note: * When rated current is4000A, forced air cooling is required.
*All technical parameters are data from type tests, rather than theoretical calculation.
※Motor-operated chassis vehicle of circuit breaker can be selected according to specific engineering requirements.
※Sensor type can be selected according to requirements for online condition monitoring on circuit breaker.